016

OC6

Lenze · 9300 Series

Hva betyr 016 ?

The drive is experiencing an I²xt overload, characterized by frequent and excessively long acceleration processes with motor overcurrent, or permanent motor overload where Imotor > Irmotor. This signals a prolonged motor overload condition.

Vanlige årsaker

  • Frequent start/stop cycles or rapid reversals of the motor with high inertial loads, exceeding the motor's thermal capacity.
  • Motor is undersized for the application's continuous torque demand or peak power requirements, leading to sustained high current.
  • Reduced cooling efficiency of the motor due to obstructed fan, dirty cooling fins, or high ambient temperature, accelerating thermal buildup.
  • Motor protection parameters (e.g., C0020 (Motor current) or C0030 (Overload factor)) are misconfigured, allowing excessive current for too long.
  • Mechanical jamming or obstruction within the driven machine causing prolonged high-current operation.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    1. Monitor motor current (A) and motor temperature (if sensor present) during a full operational cycle and compare to motor nameplate data and thermal limits.

  2. 2

    2. Verify the drive's motor data parameters (e.g., C0020 for motor rated current, C0021 for motor rated voltage) accurately match the motor nameplate.

  3. 3

    3. Increase the motor acceleration and deceleration times (e.g., C0026, C0027) to reduce peak currents during transient operations, if the process allows.

  4. 4

    4. Inspect motor cooling fins and fan for cleanliness and obstructions. Ensure proper airflow around the motor and within its terminal box.

  5. 5

    5. Use a clamp meter to measure actual motor phase currents for unbalance, which can indicate mechanical issues or motor winding problems.

Se alle koder i denne manualen (145)