162

Error in the range of the encoder.

Lenze · 9300 Series

Hva betyr 162 ?

The traversing range of the absolute encoder has been exceeded. This means the physical travel of the drive has gone beyond the measurement capabilities of the installed encoder.

Vanlige årsaker

  • Physical travel of the mechanical system has exceeded the maximum measurement range of the installed absolute encoder (e.g., single-turn limits, multi-turn beyond specified turns).
  • Incorrect encoder scaling factor (e.g., Parameter C0301 for pulses per revolution, C0302 for gear ratio) causing misinterpretation of the actual physical position.
  • Homing procedure established an incorrect zero point, leading to a calculated position outside the encoder's valid range during normal operation.
  • Encoder damage or internal fault causing it to report values outside its specified operational range.
  • System mechanics have physically moved beyond the intended safe travel, often due to an unrelated control error or collision.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    1. Verify the specified absolute encoder range (e.g., number of turns for multi-turn) and compare it against the actual mechanical travel of the axis.

  2. 2

    2. Review and correct the encoder scaling parameters (e.g., C0301, C0302) to ensure accurate position calculation.

  3. 3

    3. Re-perform the homing sequence to establish a correct zero position within the encoder's valid operating range.

  4. 4

    4. Monitor the actual encoder raw counts (if available in diagnostics, e.g., P5-07) and physical position to pinpoint where the range is exceeded.

  5. 5

    5. Check the encoder coupling for slippage or damage that could lead to misreporting of actual position relative to the motor shaft.

Se alle koder i denne manualen (145)