External monitoring triggered
Lenze · 9300 Series
Hva betyr EEr ?
An external monitoring function has been triggered via DCTRL, meaning a digital signal assigned to the TRIP-SET function has been activated. This indicates an external safety or control system has detected an issue.
Vanlige årsaker
- External safety circuit (e.g., E-stop button, light curtain) connected to a digital input (e.g., X1.1, X1.2) assigned to TRIP-SET has been activated.
- Auxiliary contact of an external protective device (e.g., motor thermal overload relay, pressure switch) wired to a digital input configured for TRIP-SET changed state.
- Faulty wiring or loose connection on the digital input terminal (e.g., X1.1, X1.2) causing an intermittent or false trigger of the external monitoring function.
- Incorrect parameterization of the digital input function (e.g., P0-01 to P0-08 assignment) for the intended external monitoring device.
- Power supply issue (e.g., 24VDC external supply) to the external monitoring device, causing its output contact to open or close incorrectly.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Identify which digital input (e.g., DI1, DI2) is configured for "TRIP-SET" in parameters P0-01 through P0-08 and check its current status in the diagnostic menu (e.g., C0001).
- 2
Inspect the external safety circuit or monitoring device connected to the identified digital input for activation (e.g., E-stop pressed, limit switch opened). Reset or rectify the external condition.
- 3
Measure the voltage between the active digital input terminal (e.g., X1.1) and the common (e.g., X1.5 or 0V) to verify the signal state (e.g., 24VDC for ON, 0VDC for OFF).
- 4
Check the wiring continuity from the external monitoring device's output contact to the drive's digital input terminal (e.g., X1.1).
- 5
Temporarily disconnect the external monitoring signal from the drive's digital input terminal (e.g., X1.1) and apply a known valid signal (e.g., 24VDC or 0VDC depending on configuration) to rule out external device failure.