H10

Heatsink temperature sensor error

Lenze · 9300 Series

Hva betyr H10 ?

The sensor for detecting the heatsink temperature is indicating undefined values. This prevents accurate monitoring of the heatsink's thermal status, potentially leading to overheating if not addressed.

Vanlige årsaker

  • Failure of the heatsink temperature sensor (e.g., NTC thermistor) itself, providing an out-of-range resistance value.
  • Broken or loose wiring connection between the heatsink temperature sensor and the control board.
  • Corrupted input or processing circuit on the control board for the temperature sensor signal.
  • External electromagnetic interference (EMI) affecting the low-voltage sensor signal wiring.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Completely power cycle the drive (disconnect all power, wait 5 minutes) to reset the internal monitoring circuits.

  2. 2

    Using a multimeter, measure the resistance of the heatsink temperature sensor directly at its terminals (e.g., X12.1, X12.2) and compare with the manufacturer's specified resistance-temperature curve (e.g., 10kOhm at 25°C).

  3. 3

    Inspect the wiring from the heatsink temperature sensor to the control board for any breaks, loose connections, or signs of heat damage.

  4. 4

    Check for any significant sources of EMI near the drive that could be affecting sensor wiring. Ensure proper grounding of the drive chassis and shielded cabling.

  5. 5

    If available, use diagnostic software to monitor the raw temperature sensor reading to determine if the reported value is consistently out of range or erratic.

Se alle koder i denne manualen (145)
Verifisert teknisk data. Sist oppdatert: March 2026