Oversetter...
Sd7

Absolute value encoder initialisation error at X8

Lenze · 9300 Series

Hva betyr Sd7 ?

The absolute value encoder at X8 has an initialisation error, is defective, or is not sending data. This may also occur if the encoder constant (C0420) for C0025=309 is altered. An uninitialised encoder can lead to uncontrolled drive movements.

Vanlige årsaker

  • Absolute value encoder power supply (e.g., 24VDC) at X8 is missing or unstable, preventing the encoder from booting up.
  • Communication link (e.g., SSI, EnDat, Hiperface) between the absolute encoder and X8 input is interrupted or shorted.
  • Encoder constant (C0420) configured for C0025 = 309 (absolute encoder) is incorrect, causing a data interpretation error.
  • Internal fault within the absolute encoder, preventing it from initializing or sending valid position data.
  • Loose or corroded connections at the X8 terminal block or the encoder's motor-mounted connector.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Power off the drive, disconnect the encoder cable from X8, and measure the encoder power supply voltage at the X8 terminals with power on.

  2. 2

    Inspect the absolute encoder cable for physical damage, continuity, and correct pinout for the specific communication protocol (e.g., SSI clock/data).

  3. 3

    Verify parameter C0025 is set to 309 for absolute encoder, and C0420 (encoder constant) matches the encoder's specified resolution/turns.

  4. 4

    Check the encoder's diagnostic LEDs (if present) for any fault indications during power-up or operation.

  5. 5

    Ensure the encoder is properly mechanically mounted and aligned, as some absolute encoders require correct initial physical positioning.

  6. 6

    Cycle power to the encoder and drive in sequence, then initiate an encoder re-initialization routine via the drive's keypad or software.

Se alle koder i denne manualen (145)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder