Oversetter...
x032

LP1 Motor phase failure

Lenze · 9300 Series

Hva betyr x032 ?

One of the current-carrying motor phases has failed. This monitoring function is primarily for asynchronous motors and requires the MLP1 function block to be entered in C0465. Possible causes include a faulty motor, a damaged motor cable, or a current limit value (C0599) set too low. The monitoring can be switched off via C0597.

Vanlige årsaker

  • Open circuit in one of the motor phases (U, V, or W) within the motor cable due to a broken conductor or severe mechanical damage.
  • Poor or loose connection at the motor terminal block or the drive output terminals (e.g., X2/U, X2/V, X2/W) for one of the phases.
  • Internal winding fault or open circuit within the motor itself, leading to one phase becoming disconnected.
  • Malfunctioning current sensor or monitoring circuit within the drive for a specific phase, causing a false detection of phase loss.
  • Incorrect configuration of parameter C0465, where the MLP1 function block is not properly activated or set for the motor type.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Power down the drive and disconnect the motor cable from the drive's output terminals (e.g., X2/U, X2/V, X2/W).

  2. 2

    Measure the resistance between each pair of motor phase conductors (U-V, V-W, W-U) at the drive output side of the cable. Expected readings should be similar.

  3. 3

    Measure the resistance of each motor winding at the motor terminal block (e.g., U-V, V-W, W-U). All three measurements should be identical for a healthy motor.

  4. 4

    Check the tightness and integrity of all connections at the drive's motor output terminals (X2/U, X2/V, X2/W) and the motor terminal block.

  5. 5

    Verify parameter C0465 is correctly configured for motor phase monitoring (MLP1) and matches the connected motor type (e.g., asynchronous motor).

  6. 6

    Perform an insulation resistance test on the motor windings (each phase to ground) using a megohmmeter to rule out internal winding faults.

Se alle koder i denne manualen (145)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder