Oversetter...
x065

CE4 BUS-OFF state of the system bus (CAN)

Lenze · 9300 Series

Hva betyr x065 ?

The system bus (CAN) has entered a BUS-OFF state due to an excessive number of faulty telegrams. This indicates a severe and persistent communication problem on the CAN network, which is configured via parameter C0595.

Vanlige årsaker

  • Persistent electrical noise or reflections on the CAN bus causing a high rate of bit errors and retransmissions.
  • One or more nodes on the CAN bus are faulty, constantly transmitting erroneous data or acting as a 'babbling idiot'.
  • Incorrect or missing termination resistors on the CAN bus, leading to severe signal integrity issues.
  • Grounding problems creating voltage potential differences between CAN nodes, interfering with signal integrity.
  • Severe physical damage to the CAN bus cable (e.g., short circuit between CAN_H and CAN_L, or to ground).

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    1. Power down the drive, measure resistance across CAN_H and CAN_L terminals at both ends of the CAN bus; it should be 60 Ohms with two 120 Ohm terminators.

  2. 2

    2. Use a CAN bus analyzer to identify the source of erroneous telegrams by monitoring error frames and bus load.

  3. 3

    3. Isolate potential faulty nodes by disconnecting devices one by one and monitoring the bus status until the BUS-OFF state clears.

  4. 4

    4. Check all CAN bus cable shielding for proper connection to ground at both ends, and ensure cables are routed away from noise sources.

  5. 5

    5. Verify the internal parameter C065 (CAN Bus-Off Threshold) and consider adjusting it temporarily for diagnostic purposes, with caution.

Se alle koder i denne manualen (145)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder