Oversetter...
0x7697

Parameter changes lost

Lenze · i550 Protec Drive

Hva betyr 0x7697 ?

This fault occurs when a voltage failure happens before recently changed parameter settings could be saved. All unsaved parameter changes are lost.

Vanlige årsaker

  • Power outage or transient voltage dip (brownout) occurred immediately after parameter changes were made but before a 'save' command was executed.
  • Operator forgot to issue the 'Save parameters' command (e.g., P99.00 = 2) after making modifications.
  • Control power supply (e.g., 24VDC at X1:1, X1:2) to the inverter dropped below the minimum threshold before changes were permanently stored.
  • Internal memory fault in the inverter preventing the non-volatile storage of parameters.
  • Frequent power cycling or unexpected shutdowns during commissioning without allowing sufficient time for parameter writes.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Always execute the 'Save parameters' command (e.g., P99.00 = 2) explicitly after making any parameter changes.

  2. 2

    Verify the stability of the control power supply (e.g., 24VDC) to the inverter, ensuring it does not drop below specified voltage during operation.

  3. 3

    Implement an uninterruptible power supply (UPS) for the control circuit if the environment experiences frequent power fluctuations.

  4. 4

    After making changes, allow a few seconds before initiating a power cycle to ensure sufficient time for internal write operations.

  5. 5

    If parameter changes are consistently lost even after explicit saving and stable power, consider a drive replacement due to internal memory failure.

Se alle koder i denne manualen (52)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder