User-defined fault 1
Lenze · i550 Protec Drive
Hva betyr 25217 ?
This fault indicates that the 'Activate fault 1' function has been triggered within the flexible I/O configuration. The activation specifically occurred via the input trigger selected in parameter 0x2631:043 (P400.43). This fault type typically results in the motor being brought to a standstill.
Vanlige årsaker
- External process condition or sensor activated, triggering the input configured for 'Activate fault 1' in Parameter 0x2.
- Incorrect wiring or intermittent connection to the digital input terminal assigned to 'Activate fault 1' (Parameter 0x2).
- Spurious electrical noise on the input line configured in Parameter 0x2, causing an unintended fault trigger.
- Misconfiguration of Parameter 0x2, leading to the selection of an inappropriate or always-active input source.
- Internal hardware fault on the specific digital input channel used for 'Activate fault 1'.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Identify the physical digital input terminal associated with 'Activate fault 1' as configured in Parameter 0x2.
- 2
Measure the voltage level at the identified digital input terminal (e.g., 24VDC or 0VDC) to verify its state when the fault occurs.
- 3
Verify the status and operation of the external sensor or device connected to this input, ensuring its output is as expected.
- 4
Review Parameter 0x2 settings to confirm the correct input source and logic (e.g., normally open, normally closed) are selected.
- 5
Temporarily disconnect the external signal from the digital input terminal and observe if the fault clears, indicating an external signal issue.