Analog input 2 fault
Lenze · i550 Protec Drive
Hva betyr 28802 ?
The monitoring function for analog input 2 has been triggered, as configured via parameters 0x2637:008 (P431.08) and 0x2637:009 (P431.09). This indicates an issue with the signal connected to analog input 2, potentially an out-of-range or missing signal.
Vanlige årsaker
- Analog input signal from the external device connected to Analog Input 2 is outside the configured monitoring range (P431.08, P431.09).
- Cable fault (open circuit or short circuit) in the wiring connected to Analog Input 2, resulting in an invalid signal level.
- Malfunctioning external sensor (e.g., potentiometer, temperature probe) providing an out-of-specification signal.
- Misconfiguration of the monitoring thresholds in parameters 0x2637:008 (P431.08) and 0x2637:009 (P431.09).
- Electromagnetic interference (EMI) or ground loop issues affecting the signal integrity on Analog Input 2.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Measure the actual signal voltage or current at the Analog Input 2 terminals (e.g., X3.3, X3.4) to confirm its value.
- 2
Check the output of the sensor or transducer connected to Analog Input 2 directly at its terminals for expected signal levels.
- 3
Verify the wiring continuity and shielding from the sensor to Analog Input 2 for damage or loose connections.
- 4
Review parameters 0x2637:008 (P431.08) and 0x2637:009 (P431.09) to ensure they are appropriate for the expected signal range.
- 5
Disconnect the external signal and apply a known test voltage or current to Analog Input 2 to check the drive's input circuit functionality.