65292

Motor phase failure phase W

Lenze · i550 Protec Drive

Hva betyr 65292 ?

A failure specifically of motor phase W has been detected. This indicates an open circuit in the wiring for phase W between the inverter and the motor, or an issue within the motor's W-phase winding. The error can only be reset after a 2-second blocking time.

Vanlige årsaker

  • Broken conductor in motor cable phase W between the inverter output (W) and motor terminal (W1).
  • Loose electrical connection at inverter output terminal W or motor terminal W1.
  • Internal open circuit in the motor's W-phase winding.
  • Failure of the inverter's internal power switching device (IGBT) responsible for phase W output.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    De-energize the drive and lock out power at the main disconnect.

  2. 2

    Disconnect the motor cable from the inverter's U, V, W output terminals.

  3. 3

    Measure the resistance between inverter output terminals U and W, and V and W using a multimeter; expect infinite resistance (open circuit).

  4. 4

    Measure the resistance of the motor's W-phase winding by disconnecting the motor cable from the motor and measuring between motor terminals U1-V1, U1-W1, and V1-W1; verify balanced, low resistance readings.

  5. 5

    Check for continuity of the motor cable conductor for phase W using a multimeter, measuring between the inverter-side W conductor and the motor-side W1 conductor.

Se alle koder i denne manualen (52)