Internal board fault
Mitsubishi Electric · FR E700
Hva betyr E.PE2 ?
This internal board fault trips the inverter when there is an incorrect combination or mismatch between the control board and the main circuit board. This indicates a serious hardware incompatibility or assembly error. The inverter cannot operate safely under these conditions.
Vanlige årsaker
- Control circuit board installed is not compatible with the main power circuit board (e.g., different generations or power ratings).
- Incorrect firmware loaded onto the control board for the specific main circuit hardware configuration.
- Loose or damaged connection ribbon cable between the control board and the main power board.
- Internal component failure on either the control board or main power board causing an incompatibility detection.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify part numbers and serial numbers of both the control board and the main power board against inverter documentation for compatibility.
- 2
Power down the inverter, then physically disconnect and reconnect the ribbon cable(s) that link the control board to the main power board.
- 3
Check for any bent pins or damage on the connectors of the ribbon cables and the board interfaces.
- 4
Confirm that the firmware version on the control board is the correct one for the installed main power section.
- 5
Measure resistance between communication lines on the ribbon cable to identify any broken traces or short circuits.