Stedy Spd OC
Overcurrent shut-off during constant speed
Mitsubishi Electric · FR-E500 Inverter
Hva betyr Stedy Spd OC ?
The inverter output is shut off because the output current reached or exceeded approximately 200% of the rated current while operating at a constant speed. This suggests a sudden increase in load or a fault in the motor/wiring during stable operation.
Vanlige årsaker
- Sudden, unexpected increase in mechanical load on the motor.
- Output short-circuit or ground fault occurring during constant speed operation.
- Motor experiencing mechanical binding or resistance during operation.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Monitor the motor's mechanical load for sudden changes or spikes during constant speed operation.
- 2
Measure the motor load current during constant speed and compare it to the motor nameplate rated current.
- 3
Inspect motor cable and motor terminals for signs of short-circuit or ground fault.
Verifisert teknisk data. Sist oppdatert: March 2026