Oversetter...
113XH
Input Response Time Range Error
Mitsubishi Electric · MELSEC iQ-R I/O Module
Hva betyr 113XH ?
A value outside the permissible range of 0 to 4 has been configured for the 'Input response time X' parameter, where 'X' denotes a specific input terminal. This error can also occur if the 'Input response time X' is set shorter than the calculated input dark test pulse output time, which is derived from 'Input dark test pulse OFF time' and 'Number of pulse output for input dark test'.
Vanlige årsaker
- The 'Input response time X' parameter for a specific input terminal X is set to a value less than 0.
- The 'Input response time X' parameter for a specific input terminal X is set to a value greater than 4.
- The 'Input response time X' parameter is set to a shorter duration than the 'Input dark test pulse output time' (Input dark test pulse OFF time × ((Number of pulse output for input dark test × 2) - 1)).
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Set the 'Input response time X' parameter within the valid range from 0 to 4 for the affected input terminal.
- 2
Ensure the 'Input response time X' is set to a longer time than the calculated 'Input dark test pulse output time'.
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: Mitsubishi Electric MELSEC iQ-R I/O Module