3060H

Module configuration error

Mitsubishi Electric · MELSEC iQ-R I/O Module

Hva betyr 3060H ?

An error was detected in the configuration of the module. This may be due to incorrect physical mounting of the module or attempting to use an I/O module that does not support SIL2 mode within a safety-critical paired configuration.

Vanlige årsaker

  • Incorrect physical mounting position of the module within the rack or system.
  • An I/O module with diagnostic functions that does not support SIL2 mode was incorrectly mounted as part of a SIL2-compliant pair.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify the mounting position of each module in the system against the configuration diagram to ensure correctness.

  2. 2

    If operating in SIL2 mode, confirm that the I/O module with diagnostic functions supports SIL2 mode and is correctly installed as a compatible pair.

Se alle koder i denne manualen (56)
Verifisert teknisk data. Sist oppdatert: March 2026