TRANSISTOR-NO-OFF-MINUTE-CURRENT
Transistor Output Not Turning Off (Minute Current)
Mitsubishi Electric · MELSEC iQ-R I/O Module
Hva betyr TRANSISTOR-NO-OFF-MINUTE-CURRENT ?
A load connected to a transistor output module fails to turn off, or may even turn on unexpectedly, when it operates with a minute current (0.1mA or lower). This behavior is attributed to the inherent leakage current present in the transistor output, which is sufficient to activate such low-current loads.
Vanlige årsaker
- The connected load requires a very low operating current (0.1mA or lower).
- Leakage current from the transistor output itself is enough to energize or partially energize the minute current load.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Connect a resistor (several tens or hundreds of kΩ) in parallel across the load terminals. This provides a path for the transistor's leakage current, ensuring the load deactivates completely.
Verifisert teknisk data. Sist oppdatert: March 2026