CC-Link IE Field Network Module Major Error
Mitsubishi Electric · MELSEC iQ-R Module Dedicated Instructions
Hva betyr 3C0FH ?
This major error occurs in the network module upon successful completion of the G(P).CCPASET instruction. It is specifically observed when an engineering tool version 1.080J or later is used in conjunction with older firmware versions of the CC-Link IE Field Network master/local module or the CPU module within a redundant configuration. This error indicates a compatibility issue leading to instability in the network module.
Vanlige årsaker
- Using G(P).CCPASET instruction with an engineering tool version 1.080J or later.
- CC-Link IE Field Network master/local module firmware version is 58 or earlier.
- CPU module firmware version is 03 or earlier.
- Operating the system in a redundant configuration under these specific firmware and software version combinations.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Avoid using the G(P).CCPASET instruction if the engineering tool is version 1.080J or later AND the CC-Link IE Field Network module firmware is 58 or earlier, OR the CPU module firmware is 03 or earlier, in a redundant configuration.