Indoor/Outdoor Miswiring (Converse) or Disconnection
Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit
Hva betyr Eb ?
The connecting wiring between the indoor and outdoor units has been miswired (converse wiring) or a disconnection has occurred. This critical fault prevents proper communication and control between the units, leading to system malfunction.
Vanlige årsaker
- Reversed wiring connections between indoor and outdoor units.
- Disconnection in the communication wiring.
- Faulty wiring harness or connectors.
- Incorrect cable type used for communication.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check the connecting wiring between the indoor and outdoor units for correct phase and signal line connections.
- 2
Verify the continuity of the connecting wire, specifically checking for any breaks or disconnections in the S3 line.
- 3
Inspect the indoor controller board for any visible defects or damage.
- 4
Inspect the outdoor controller circuit board for any visible defects or damage.