0x0400 to 0x040F
CPU Bus Unit Setting Error
Omron · CJ-series CJ2 CPU Unit
Hva betyr 0x0400 to 0x040F ?
An installed CPU Bus Unit does not match the CPU Bus Unit registered in the I/O tables. This error indicates a mismatch between the physical hardware and the configured settings. Flag A402.03 and Auxiliary Area A427 indicate the error and the problem unit number respectively.
Vanlige årsaker
- Installed CPU Bus Unit does not match the registered I/O table entry.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Change the registered I/O table using CX-Programmer to match the physically installed CPU Bus Unit.