Oversetter...
0x80F0
Program Error
Omron · CJ-series CJ2 CPU Unit
Hva betyr 0x80F0 ?
A general program error has occurred within the CJ2 CPU Unit, indicating incorrect program logic or an unrecoverable runtime issue. The program will stop, and the address at which the stop occurred will be output to A298 and A299. Specific sub-error flags (A295.xx) provide more detailed diagnostic information.
Vanlige årsaker
- The PLC program contains logical or structural mistakes.
- A specific program sub-error has been triggered (e.g., No END, UM overflow, Task error, Illegal access, Indirect DM/EM BCD error, Instruction error, Illegal instruction).
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check program error information using A298 and A299 to determine the program stop address.
- 2
Consult A295 error flags for specific sub-error details.
- 3
Correct the identified program mistake using a programming device.
- 4
Clear the error after correction.
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: Omron CJ-series CJ2 CPU Unit