Oversetter...
225

2nd Lower Limit Exceeds 2nd Multi-step Speed Reference 0

Omron · MX2 Inverter

Hva betyr 225 ?

For the second motor settings, this warning indicates that the 2nd frequency lower limit (A262) is set higher than the 2nd Multi-step speed reference 0 (A220) or the output frequency setting (F001). This creates a logical inconsistency for the alternative motor profile's minimum speed, potentially restricting the operation of the second motor.

Vanlige årsaker

  • Parameter A262 (2nd frequency lower limit) is configured to a value higher than the 2nd Multi-step speed reference 0 (A220).
  • The minimum operating frequency (A262) for the second motor is set above the intended nominal speed reference (A220).
  • The current output frequency (F001) is below the configured lower limit A262 while A262 exceeds A220, creating an illogical operational range.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Read the current values of parameter A262 (2nd frequency lower limit), A220 (2nd Multi-step speed reference 0), and F001 (Output frequency setting).

  2. 2

    Adjust parameter A262 to be less than or equal to parameter A220, ensuring the lower limit is below the multi-step speed reference.

  3. 3

    Alternatively, if the A220 multi-step speed reference is too low, increase A220 to a value greater than or equal to A262.

  4. 4

    Store the new parameter values in the drive's memory and cycle power to the drive.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder