00130000 hex
Main Memory Check Error
Omron · NX-series CPU Unit
Hva betyr 00130000 hex ?
An error was detected in the memory check of the main memory in the CPU Unit's PLC Function Module. This error is continuously detected, indicating a major fault level, and will stop user program execution and controller operation.
Vanlige årsaker
- A conductive material has gotten inside the CPU Unit.
- Noise causing data corruption in memory, microcomputer malfunctioning, or memory write circuit malfunctioning.
- A software error.
- Data corruption caused by cosmic rays or radiation.
- CPU Unit hardware failure (memory element failure, memory peripheral circuit failure).
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
If conductive material is suspected, blow out the CPU Unit with air.
- 2
Ensure the control panel is closed during operation and avoid metal working nearby.
- 3
If noise is suspected, check the FG (Frame Ground) and power supply lines, then implement noise countermeasures.
- 4
Cycle the power to the Controller; if the error persists or occurs frequently, replace the CPU Unit.
- 5
Perform regular inspections of the CPU Unit's memory and peripheral circuits.