Oversetter...
100B0000 hex

Non-volatile Memory Data Corrupted

Omron · NX-series CPU Unit

Hva betyr 100B0000 hex ?

A critical file required by the Controller, stored in non-volatile memory, is either missing or has become corrupted. This error is detected at power-on or during a Controller reset, leading to a major fault level that stops both the user program and Controller operation.

Vanlige årsaker

  • The Controller's power supply was interrupted or turned OFF while the BUSY indicator was lit, indicating an active memory operation.
  • Momentary power interruption to the Controller while the BUSY indicator was lit.
  • Failure of the CPU Unit hardware.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Perform a Memory All Clear operation on the Controller and then download the project from Sysmac Studio.

  2. 2

    Measure the incoming power supply voltage and frequency to the Controller. Ensure it consistently meets the specified rated voltage and frequency for stable operation.

  3. 3

    If the error persists after performing memory clear and verifying power supply, replace the CPU Unit.

Se alle koder i denne manualen (17)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder