Simultaneous Origin Proximity and Limit Inputs
Omron · SYSMAC CJ Series PLC
Hva betyr 0204 ?
This fault occurs during an origin search when the origin proximity input signal and the limit input signal in the search direction are being input simultaneously. This indicates a contradiction where a proximity signal is detected at the same time as a hard limit in the direction of travel, potentially causing an emergency stop.
Vanlige årsaker
- Miswiring of the origin proximity input signal or the limit input signal, causing incorrect signal detection.
- Incorrect 'Origin Proximity Input Signal Type' or 'Limit Signal Type' (NC or NO) configured in PLC Setup for either sensor.
- Mechanical interference causing both the origin proximity sensor and the limit switch to trigger simultaneously.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Inspect the wiring of both the origin proximity input signal and the limit input signal in the search direction for any short circuits, breaks, or incorrect connections.
- 2
Access the PLC Setup 'I/O Module Tab Page' using CX-Programmer and verify both the 'Origin Proximity Input Signal Type' and 'Limit Signal Type' settings (NC or NO) match the installed sensors.
- 3
Examine the physical mounting and alignment of the origin proximity sensor and the limit switch to ensure they cannot be triggered simultaneously under normal operating conditions.
- 4
Initiate an origin search again from the HMI or programming software.