Oversetter...
0205

Limit Input Signal Already Being Input

Omron · SYSMAC CJ Series PLC

Hva betyr 0205 ?

This fault indicates one of two conditions: either the limit input signal is already active in the origin search direction when a search is attempted, or during a search without proximity input, both the Origin Input Signal and the Limit Input Signal in the opposite direction from the search were ON simultaneously. This prevents the origin search from starting or proceeding correctly due to an initial, conflicting limit condition, resulting in an emergency stop.

Vanlige årsaker

  • The limit switch in the intended origin search direction is physically activated before the origin search begins.
  • Incorrect wiring of the limit input signal, causing a constant active state.
  • Incorrect 'I/O settings' or 'Limit Signal Type' (NC or NO) configured in PLC Setup.
  • If not using proximity input, both 'Origin Input Signal' and 'Limit Input Signal' for the opposite direction are simultaneously active due to misconfiguration or wiring.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Inspect the wiring of the limit input signal for breaks, shorts, or loose connections, ensuring correct termination.

  2. 2

    Physically verify that the limit switch in the intended origin search direction is not activated before attempting the origin search. If active, manually move the axis to disengage it.

  3. 3

    Access the PLC Setup 'I/O Module Tab Page' using CX-Programmer and review the 'I/O settings' and 'Limit Signal Type' (NC or NO) for accuracy against the system's electrical design.

  4. 4

    If an origin search not using proximity input is configured, confirm that the 'Origin Input Signal' and the 'Limit Input Signal' for the *opposite* direction of search are not simultaneously active before starting the search.

  5. 5

    Initiate an origin search again from the HMI or programming software.

Se alle koder i denne manualen (20)
Verifisert teknisk data. Sist oppdatert: March 2026