Special I/O Unit Number Duplication Error
Omron · SYSMAC CJ2 CPU Unit
Hva betyr A401.13 ?
This fault occurs when a Special I/O Unit's unit number is duplicated, or when a Special I/O Unit's allocated memory words conflict with a Basic I/O Unit on an Expansion Rack due to an incorrect starting word setting. When this error occurs, the CPU Unit operation will stop, and the ERR/ALM indicator on the front of the CPU Unit will light. The Duplication Error Flag (A401.13) and the corresponding specific unit flag (A411.00 to A416.15) will be set to ON.
Vanlige årsaker
- Two or more Special I/O Units are configured with the same unit number (00-95).
- A Special I/O Unit's allocated memory words conflict with a Basic I/O Unit on an Expansion Rack due to incorrect Expansion Rack starting word settings.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Identify the conflicting unit numbers by checking the status of bits A411.00 to A416.15.
- 2
Verify and correct the unit number settings for all Special I/O Units to ensure each is unique (00-95).
- 3
Review the Expansion Rack's starting word settings to prevent overlap with Special I/O Unit word allocations.
- 4
Clear the error flag (A401.13) after correcting the duplication.