CPU Bus Unit Setting Error
Omron · SYSMAC CJ2 CPU Unit
Hva betyr A402.03 ?
This fault indicates a setting error for a CPU Bus Unit. When an CPU Bus Unit Setting Error occurs, A402.03 and the bit in A427 corresponding to the Unit's unit number (0-F) are turned ON. The CPU Unit will continue operating, and the ERR/ALM indicator on the front of the CPU Unit will flash. These flags are refreshed when power is turned ON or I/O is recognized.
Vanlige årsaker
- Incorrect configuration parameters or settings for a CPU Bus Unit.
- Mismatched hardware or software settings for the CPU Bus Unit.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Identify the specific CPU Bus Unit with the setting error by checking bits A427.00 to A427.15.
- 2
Compare the configured settings for the identified CPU Bus Unit in the CX-Programmer with the actual hardware.
- 3
Reconfigure the CPU Bus Unit settings to match the expected parameters.
- 4
Cycle power or re-recognize I/O to refresh the status after correcting settings.