A402.13

Duplicate Refresh Error

Omron · SYSMAC CJ2 CPU Unit

Hva betyr A402.13 ?

This fault occurs when duplicated refreshing is performed for a Special I/O Unit. When the Duplicate Refresh Error Flag (A402.13) is ON, bit A426.15 indicates the cause of the error, and bits A426.00 to A426.11 contain the unit number (0-95) of the affected Special I/O Unit. The CPU Unit will continue operating, and the ERR/ALM indicator on the front of the CPU Unit will flash.

Vanlige årsaker

  • Configuration error leading to a Special I/O Unit's refresh being duplicated.
  • Incorrect I/O table or PLC Setup settings for a Special I/O Unit.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Identify the affected Special I/O Unit by reading the unit number from A426.00 to A426.11.

  2. 2

    Review the PLC I/O table and configuration settings for the identified Special I/O Unit.

  3. 3

    Ensure that the refreshing mechanism for the Special I/O Unit is configured uniquely.

  4. 4

    Clear the error flags (A402.13, A426.15) and the unit number bits (A426.00 to A426.11) after resolving the configuration issue.

Se alle koder i denne manualen (27)
Verifisert teknisk data. Sist oppdatert: March 2026