Omron · SYSMAC CJ2 CPU Unit

Hva betyr A528.02 ?

This flag turns ON when a parity error occurs during RS-232C communication. This indicates a data transmission integrity issue at the RS-232C port. This error flag is valid in Serial Gateway mode.

Vanlige årsaker

  • Incorrect parity settings configured on the RS-232C port or the connected device
  • Noise or interference on the RS-232C communication line
  • Faulty RS-232C cable or connector

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify the parity setting for the RS-232C port in the PLC's communication parameters matches the connected device's settings

  2. 2

    Inspect the RS-232C cable for damage or loose connections

  3. 3

    Measure voltage levels on the RS-232C communication lines to check for noise or signal integrity issues

  4. 4

    Restart the RS-232C port by turning ON the Serial Port Restart Bit (A526.00) from OFF to ON