Oversetter...
406

LOW LINE ALARM

Otis · DSD 412 DC Elevator Drive

Hva betyr 406 ?

The input AC line voltage sagged more than 10% below the nominal line voltage as set at parameter #9. This does not shut down the drive but is an indication that work is needed to avoid future F904 Low Line faults.

Vanlige årsaker

  • Input AC line voltage sagged more than 10% below nominal.
  • Nominal line voltage (parameter #9) set incorrectly for the supply.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure the input AC line voltage.

  2. 2

    Check and correct the setting of parameter #9 (nominal line voltage).

  3. 3

    Investigate the AC power supply for voltage sags or instability.

Se alle koder i denne manualen (48)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Otis DSD 412 DC Elevator Drive