406
LOW LINE ALARM
Otis · DSD 412 DC Elevator Drive
Hva betyr 406 ?
The input AC line voltage sagged more than 10% below the nominal line voltage as set at parameter #9. This does not shut down the drive but is an indication that work is needed to avoid future F904 Low Line faults.
Vanlige årsaker
- Input AC line voltage sagged more than 10% below nominal.
- Nominal line voltage (parameter #9) set incorrectly for the supply.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Measure the input AC line voltage.
- 2
Check and correct the setting of parameter #9 (nominal line voltage).
- 3
Investigate the AC power supply for voltage sags or instability.