RIPPLE FAULT

Otis · DSD 412 DC Elevator Drive

Hva betyr 909 ?

Repeated instances of high peak-to-average motor armature current are detected. This condition can be caused by defective hardware, inadequate regulator tuning, or other oscillatory operating conditions.

Vanlige årsaker

  • Defective hardware components, which can be diagnosed using the PCU Diagnostics CDU function #998.
  • Poor tuning or configuration of the drive's current regulator.
  • Other conditions leading to oscillatory operation within the motor or drive system.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Execute the PCU Diagnostics CDU function #998 to identify any defective hardware.

  2. 2

    Review and adjust the drive's regulator tuning parameters to stabilize current ripple.