406

LOW LINE ALARM

Otis · DSD 412 Elevator System

Hva betyr 406 ?

This alarm indicates that the input AC line voltage has sagged more than 10% below the nominal line voltage, as configured by parameter #9. This is a warning and does not automatically shut down the DSD 412 drive, but it suggests that preventative action may be required to avoid future F904 Low Line shutdown faults.

Vanlige årsaker

  • Insufficient or sagging 3 Phase Input AC Line Voltage.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure the 3 Phase Input AC Line Voltage to verify its stability and level.

  2. 2

    Verify that the nominal line voltage setting in parameter #9 accurately reflects the system's requirements.