900

PCU LOOP FAULT

Otis · DSD 412 Elevator System

Hva betyr 900 ?

The contactor did not close or opened unexpectedly, or the motor voltage exceeded 30% of rated motor voltage #7 during Self-Tune #997. This fault sets the Severe Fault flag and forces the DSD 412 current reference to zero, leading to a drive shutdown.

Vanlige årsaker

  • Contactor auxiliary feedback circuit issue to TB1-7.
  • Contactor or LPR (Line Power Relay) coils not operating properly.
  • Loss of power to LPR from the power supply at TB3-5 (this will be momentary until F900 occurs).
  • Internal relay failure if no power is detected at TB3-5.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check the contactor auxiliary feedback circuit to TB1-7.

  2. 2

    Check contactor and LPR coils for proper operation.

  3. 3

    Verify power is being applied to LPR from the power supply at TB3-5.

  4. 4

    If no power at TB3-5, replace the A4 Power Supply PCB, as an internal relay failure is suspected.