915

PARAMETER SETUP FAULT

Otis · DSD 412 Elevator System

Hva betyr 915 ?

One of the following parameters is not within the acceptable range of the chassis hardware: Rated Volts #7 or #9, or Rated Current #3 or #50. This fault requires a DSD power down.

Vanlige årsaker

  • Incorrect parameter data entered for Rated Volts (#7 or #9) or Rated Current (#3 or #50).

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Enter the correct parameter data for #7, #9, #3, or #50.

  2. 2

    Save the changes to NVRAM.

  3. 3

    Reset the drive and re-start.