EF2
Ground Fault
Schindler · Altivar 212 Variable Frequency Drive
Hva betyr EF2 ?
This fault signals a ground fault in the motor or the motor cables, indicating an insulation breakdown or improper grounding in the output circuit of the Altivar 212 drive.
Vanlige årsaker
- Ground fault in the motor windings.
- Ground fault in the motor cables.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Measure insulation resistance between motor phases and ground using a megger.
- 2
Measure insulation resistance between motor cables and ground using a megger.
- 3
Inspect motor and motor cables for physical damage or wear causing a ground path.