OC1
Overcurrent During Acceleration
Schindler · Altivar 212 Variable Frequency Drive
Hva betyr OC1 ?
This fault indicates an overcurrent condition during motor acceleration by the Altivar 212 drive, often caused by excessively short acceleration times, incorrect motor control settings, or high-inertia loads.
Vanlige årsaker
- Acceleration time is too short (ACC or F500).
- Incorrect setting of [Mot cont. mode sel.] (Pt).
- Drive is starting into a rotating load.
- Drive is powering a low impedance motor.
- Ground fault in the motor or cables.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Increase the acceleration time parameters (ACC or F500).
- 2
Select the correct setting for parameter [Mot cont. mode sel.] (Pt).
- 3
Enable catch on the fly function (F301).
- 4
Adjust the switching frequency parameter F300.
- 5
Set parameter F316 ([Switch. freq. mode]) to 1 or 3.