OCL

Short Circuit Motor Cable at Start

Schindler · Altivar 212 Variable Frequency Drive

Hva betyr OCL ?

This fault indicates a phase-to-phase output short circuit or a low motor impedance detected in the motor or its wiring during startup by the Altivar 212 drive.

Vanlige årsaker

  • Phase-to-phase output short circuit in motor or cables.
  • Motor impedance is too low.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Use a 1000 V testing tool (megger) to check the motor windings for phase-to-phase insulation resistance.

  2. 2

    Use a 1000 V testing tool (megger) to check the motor cables for phase-to-phase insulation resistance.