OL2

Motor Overload

Schindler · Altivar 212 Variable Frequency Drive

Hva betyr OL2 ?

This fault indicates a motor overload condition, potentially caused by incorrect motor control settings, a jammed motor, continuous low-speed operation, or excessive load from the Altivar 212 drive.

Vanlige årsaker

  • Incorrect setting of [Mot cont. mode sel.] (Pt).
  • The motor is jammed or mechanically binding.
  • Continuous low-speed operation is performed.
  • Excessive mechanical load is applied to the motor.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Select the correct setting for parameter [Mot cont. mode sel.] (Pt).

  2. 2

    Check the mechanical load for any binding or obstructions.

  3. 3

    Adjust parameter OLM ([Motor overload prot]) to the overload level that the motor can withstand during low speed operation.