UP1

Undervoltage

Schindler · Altivar 212 Variable Frequency Drive

Hva betyr UP1 ?

This fault indicates that the input voltage to the Altivar 212 drive is too low, potentially causing instability or improper operation. This can lead to a drive trip to prevent damage.

Vanlige årsaker

  • The input voltage to the drive is too low.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure the input voltage at the drive terminals (R/L1, S/L2, T/L3) and rectify the supply trouble.

  2. 2

    Select the correct setting for parameter F627 ([Undervolt detect.]).

  3. 3

    Enable catch on the fly function (F301).

  4. 4

    Set parameter F302 ([Supply loss behav.]) to 2 (Freewheel).

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026