Oversetter...
LFF

4-20 mA Loss

Schneider Electric · Altivar 312 Variable Frequency Drive

Hva betyr LFF ?

This fault occurs when the drive detects a loss of the 4-20 mA analog input signal, which is typically used for speed reference or feedback. This usually means a broken wire, a disconnected sensor, or a faulty analog signal source, causing the drive to lose its command reference and potentially stop or operate incorrectly. It can also be referred to as APL (4-20mA Loss).

Vanlige årsaker

  • Broken wire or loose connection in the 4-20 mA analog input signal loop (e.g., terminals AI1, AI2, AIGND).
  • Faulty external sensor or transducer (e.g., pressure sensor, flow meter) providing the 4-20 mA signal.
  • Loss of power to the 4-20 mA sensor or the external control system supplying the signal.
  • Incorrect drive parameter setting for the 4-20 mA input (e.g., minimum current level P4-10 or P4-14).
  • Internal drive analog input circuit failure or component malfunction.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    1. Measure the current directly at the drive's analog input terminals (e.g., AI1 to AIGND) using a multimeter in series.

  2. 2

    2. Trace the 4-20 mA wiring from the drive back to the sensor/source; check for continuity and secure connections.

  3. 3

    3. Verify the power supply to the external 4-20 mA sensor or transducer.

  4. 4

    4. Check Parameter P4-10 (AI1 min current) or P4-14 (AI2 min current) to ensure the drive's low-current threshold is correctly set (e.g., to 4 mA).

  5. 5

    5. If possible, inject a known 4-20 mA signal from a current calibrator into the drive's analog input to test the drive's internal circuitry.

Se alle koder i denne manualen (31)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Schneider Electric Altivar 312 Variable Frequency Drive