Oversetter...
PHF

INPUT PHASE LOSS

Schneider Electric · ATV32HD11N4 Variable Speed Drive

Hva betyr PHF ?

This fault signifies that the drive is incorrectly supplied, has a blown fuse on one phase, or is a three-phase ATV312 unit mistakenly used on a single-phase line supply. It can also be caused by an unbalanced load and typically only operates when the drive is under load. Unresolved input phase loss can lead to drive component stress, rectifier failure, and prevents proper operation.

Vanlige årsaker

  • Blown fuse on one or more incoming phases (L1, L2, L3) supplying the drive.
  • Open circuit breaker pole or tripped protective device in the main supply path to the drive.
  • Loose connection or corroded terminal on one of the incoming phases at the drive input terminals (L1, L2, L3) or upstream.
  • Main contactor or input isolation switch with one pole open or a high resistance contact.
  • Drive is a three-phase unit connected to a single-phase supply without proper configuration or if the drive is not rated for single-phase operation.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    1. Measure the incoming line voltages (L1-L2, L2-L3, L3-L1) at the drive input terminals using a multimeter; confirm all three phases are present and balanced.

  2. 2

    2. Inspect all fuses in the input power circuit (main fuses, control circuit fuses) for continuity using an ohmmeter; replace any blown fuses with specified ratings.

  3. 3

    3. Tighten all input power terminal screws (L1, L2, L3) on the drive and at any upstream contactors, circuit breakers, or terminal blocks.

  4. 4

    4. If an input contactor is used, manually operate it to check for proper pole closure and measure voltage across each contact (should be 0V when closed).

  5. 5

    5. Check drive parameters for single-phase operation settings (e.g., Parameter LIS) if applicable, and ensure drive is rated for single-phase supply if connected that way.

  6. 6

    6. Verify the integrity of the main supply cable by performing a continuity test from the source to the drive input terminals.

Se alle koder i denne manualen (25)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Schneider Electric ATV32HD11N4 Variable Speed Drive