AI L2 Over Voltage
Schneider Electric · XW Pro NA Operation Guide
Hva betyr F32 ?
This fault indicates an L2 over-voltage condition (130 V) detected by the anti-islanding protection, triggering a slow disconnect. This mechanism ensures the inverter disconnects from an unstable grid, protecting both the inverter and grid from potential damage due to excessive voltage.
Vanlige årsaker
- Grid L2-Neutral voltage exceeding 130 V for a sustained period, indicating persistent grid voltage instability or a utility over-voltage condition.
- Gradual voltage creep on phase L2 due to an imbalanced grid or nearby generator operations, exceeding the slow trip threshold.
- Inverter's L2 voltage sensing circuit drifting out of calibration or experiencing intermittent measurement errors over time.
- Anti-islanding parameter P_AI_L2_Volt_Max_Slow set too close to nominal, causing frequent trips during minor voltage fluctuations.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Using a true RMS multimeter, continuously monitor the L2-Neutral voltage at the inverter's AC input terminal L2 over several hours to detect persistent high voltage.
- 2
Compare the sustained L2-Neutral voltage readings against the specified 130 V trip threshold and the inverter's P_AI_L2_Volt_Slow parameter.
- 3
Verify that the neutral conductor connection to the inverter (Terminal N) and the L2 phase terminal (Terminal L2) are secure and free from corrosion.
- 4
Contact the utility provider to report sustained high voltage conditions on phase L2 at your site and request a grid voltage stability check.
- 5
If external voltage is stable, verify the inverter's internal L2 voltage measurement offset parameter (e.g., P_AI_L2_Volt_Offset) for potential misconfiguration.