FET2 Over Temperature Shutdown
Schneider Electric · XW Pro NA Operation Guide
Hva betyr F58 ?
This Automatic Fault occurs when the internal temperature of FET2 exceeds 105 °C, triggering a shutdown to protect the inverter's power components. The fault clears automatically when the temperature drops to 75 °C, similar to F57.
Vanlige årsaker
- Restricted airflow around the inverter's cooling fins or fan intake/exhaust vents due to dust accumulation or obstruction.
- Malfunctioning cooling fan (e.g., seized motor, broken blades, low RPM) not effectively dissipating heat from the FET2 heatsink.
- Sustained operation at or above the inverter's rated continuous power output, leading to excessive heat generation, potentially on one phase.
- Degraded thermal paste or inadequate contact between FET2 package and its heatsink.
- Internal fault within FET2 or its associated gate drive circuit causing increased conduction losses.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
1. Power down the inverter, disconnect AC and DC sources, and allow components to cool (e.g., 30 minutes).
- 2
2. Inspect all cooling fan(s) for proper operation, verify fan rotation, and clean any dust buildup from fan blades and heatsink fins using compressed air.
- 3
3. Measure the ambient temperature around the inverter and ensure it is within the manufacturer's specified operating range (e.g., -20°C to +45°C).
- 4
4. Verify that the load connected to the inverter's AC output does not exceed its continuous power rating (e.g., check output current via display or clamp meter).
- 5
5. Check for loose mounting screws or improper seating of FET2 to its heatsink, ensuring adequate thermal transfer.