Start Condition Error

SEW Eurodrive · MOVIMOT® MM..D with AC Motor DT/DV / Operating Instruc

Hva betyr 81 ?

This fault occurs when the motor cannot be supplied with the correct amount of current during the pre-magnetizing time, particularly in hoist applications. This indicates an impedance mismatch or inadequate current capacity, preventing proper motor startup.

Vanlige årsaker

  • Rated motor power is too small in relation to the rated inverter power.
  • Motor cable cross-section is too small.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check the connection between the MOVIMOT inverter and the motor, verifying cable cross-section.

  2. 2

    Verify that the rated motor power is appropriately matched with the rated inverter power.

  3. 3

    Reset the fault by switching off and then switching on the DC 24V supply voltage.

  4. 4

    Reset the error via the error reset function.