F03

Ground fault

SEW Eurodrive · MOVITRAC 07B System

Hva betyr F03 ?

An immediate switch-off with inhibit occurs due to a ground fault. This can be caused by a ground fault in the motor, the inverter itself, or the motor supply lead. It may also be a symptom of an overcurrent condition.

Vanlige årsaker

  • Ground fault in the motor
  • Ground fault in the inverter
  • Ground fault in the motor supply lead
  • Overcurrent (refer to F01 causes)

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Replace the motor if a ground fault is detected within it

  2. 2

    Replace the MOVITRAC® B inverter if it has an internal ground fault

  3. 3

    Eliminate any ground fault found in the motor supply lead

  4. 4

    Refer to troubleshooting steps for F01 if overcurrent is a contributing factor

Se alle koder i denne manualen (41)