F01625

Sign-of-life error in the Safety data

Siemens · SINAMICS G120

Hva betyr F01625 ?

An error has occurred with the safety data's sign-of-life signal, indicating a potential communication or integrity issue within the safety functions. This can be caused by EMC disturbances or an inadmissible voltage at a Control Unit digital output. Such an error critically impacts the system's ability to maintain safe operation.

Vanlige årsaker

  • Electromagnetic compatibility (EMC) interference affecting the safety communication bus or internal Control Unit communication.
  • Incorrect or inadequate shielding of safety communication cables (e.g., PROFIsafe line).
  • Processor overload or internal timing issues within the Control Unit preventing timely processing of safety sign-of-life signals.
  • Temporary communication disruption between the safety Control Unit and the safety application (e.g., Safety CPU).
  • Inconsistent safety configuration data (e.g., checksum mismatch) between the drive and the higher-level safety controller.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Inspect and verify the shielding termination for all safety communication cables (e.g., PROFINET/PROFIBUS) at both the drive and controller ends.

  2. 2

    Check for potential sources of high-frequency interference (e.g., unsuppressed contactors, welding equipment) near the drive or safety communication lines.

  3. 3

    Verify the drive's firmware version is compatible with the safety PLC firmware and the configured safety functions.

  4. 4

    Perform a power cycle of the drive and the associated safety controller to re-initialize communication.

  5. 5

    Review event logs (e.g., drive fault memory and safety PLC diagnostic buffer) for concurrent communication issues or other related faults.