A30920

Temperature sensor fault

Siemens · SINAMICS G120C Variable Speed Drive

Hva betyr A30920 ?

An error occurred during the evaluation of a temperature sensor connected to the power unit. This can manifest as a wire breakage or a disconnected sensor (e.g., KTY: R > 2120 Ohm) or a measured resistance that is too low (e.g., PTC: R < 20 Ohm, KTY: R < 50 Ohm). Accurate temperature monitoring is crucial for protecting the power unit from overheating. If unaddressed, this could lead to undetected overheating and potential damage to components.

Vanlige årsaker

  • Open circuit or broken wire in the temperature sensor cable (e.g., PT100, KTY84-130) connected to the power unit terminal block.
  • Temperature sensor resistance measurement (e.g., KTY84-130) exceeding the upper threshold (e.g., 2120 Ohm) indicating a high resistance fault.
  • Short circuit in the temperature sensor cable or sensor element, resulting in a resistance measurement below the lower threshold (e.g., < 100 Ohm for KTY).
  • Corroded or loose connection at the power unit sensor input terminals (e.g., X10-1, X10-2), increasing contact resistance.
  • Incorrect sensor type configured in drive parameter P0601 (e.g., NTC selected instead of KTY84-130).

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    De-energize the power unit and measure the resistance of the connected temperature sensor directly at its terminals (e.g., X10) using a calibrated multimeter.

  2. 2

    Compare the measured sensor resistance against the manufacturer's specified resistance curve for the actual motor temperature (e.g., KTY84-130 @ 20°C should be ~580 Ohms).

  3. 3

    Verify the continuity of the sensor cable by performing a continuity test from the sensor element to the power unit terminal block (e.g., X10) using a multimeter.

  4. 4

    Check parameter P0601 (Motor temperature sensor type) and ensure it is configured correctly for the installed sensor (e.g., 1=PT100, 2=KTY84-130).

  5. 5

    Inspect the temperature sensor cable for physical damage, pinching, or exposure to excessive heat along its entire length.

  6. 6

    Measure the insulation resistance of the temperature sensor cable to ground using a megohmmeter (e.g., 500VDC test voltage).