Oversetter...
Grid-Timeout/Grid-Fault-S
Grid Type Detection Failure
SMA · SUNNY BOY 5000US-8000US Solar Inverter
Hva betyr Grid-Timeout/Grid-Fault-S ?
The Sunny Boy SB50US-80US-IUS094030 inverter failed to detect the type of connected grid (208V, 240V, or 277V). This can be caused by incorrect wiring, especially when connecting to specific grid types.
Vanlige årsaker
- Incorrect wiring for L1 and N cables when connecting to a 277V grid.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
If connecting to a 277V grid, verify that the L1 and N cables are in the correct terminal positions.
- 2
Check the condition of the grid at the AC terminal blocks within the Sunny Boy SB50US-80US-IUS094030.
- 3
Inspect the AC disconnect between the Sunny Boy and the grid.