Ground Fault / High Leakage Current / Residual Current
SMA · Sunny Boy Solar Inverter
Hva betyr 3501/3601/3701 ?
The inverter has detected a ground fault in the PV array (3501), or the leakage current of the inverter and PV array is too high (3601), or a residual current due to temporary grounding of the PV array has been detected (3701). These conditions indicate defective or insufficient electrical insulation from the PV system to ground, potentially from a ground fault, residual current, or a malfunction causing high leakage current. The inverter will interrupt feed-in operation.
Vanlige årsaker
- Ground fault in the PV array due to damaged insulation.
- Defective or insufficient electrical insulation from the PV system to ground.
- High leakage current in the inverter and/or PV array due to a malfunction or residual current from temporary grounding.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Disconnect the inverter from all voltage sources (refer to the inverter installation manual).
- 2
Measure the voltage between the positive terminal and the ground potential (PE) of the PV array.
- 3
Measure the voltage between the negative terminal and the ground potential (PE) of the PV array.
- 4
Measure the voltage between the positive and negative terminals of the PV array.
- 5
If all measured voltages are stable AND the sum of the two voltages to ground potential is approximately equal to the voltage between the positive and negative terminals, a ground fault is present. Determine the location of the ground fault via the ratio of the two measured voltages and eliminate it.
- 6
If a definite ground fault cannot be measured by voltage, perform an insulation resistance measurement on the PV system using a measuring device with a DC input voltage range of 600 V or higher.