Brake chopper supervision
Vacon · 100 FLOW Application Guide
Hva betyr 12 ?
This fault indicates that either no brake resistor is installed, the installed brake resistor is broken, or there is a failure within the brake chopper unit itself. This prevents proper dissipation of regenerative energy.
Vanlige årsaker
- The brake chopper circuit is not functioning as expected.
- Excessive voltage detected across the brake chopper resistor.
- Failure of the brake chopper semiconductor switch.
- Brake resistor is open or shorted.
- Brake chopper duty cycle exceeded.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check the brake resistor for continuity and proper resistance value.
- 2
Verify the cabling between the frequency converter and the brake resistor for proper connection and integrity.
- 3
If the resistor and cabling are confirmed good, the chopper unit is faulty.